Electronic Camming LabVIEW Diagram
The following block diagram demonstrates using NI-Motion to perform electronic camming.
|
Tip Refer to NI-Motion\Documentation\Examples\NI-Motion User Manual\ for the LabVIEW VIs for these examples. |
|
1 Configure Camming Master |
6 Set Operation Mode |
11 Enable Camming Single Axis |
2 Configure Buffer |
7 Load Move Constraint |
12 Clear Buffer |
3 Write Buffer |
8 Load Target Position |
13 Motion Error Handler |
4 Enable Camming Single Axis |
9 Start Motion |
|
5 Wait in a Sequence Structure |
10 Wait for Move Complete |
|