Reset Module

FieldPoint Optomux Programming

Reset Module

[cmdchars] = !Z

Description

When the Reset Module is sent to a network module, it resets all I/O modules in the bank and sets the turnaround delay for all modules to zero. When this command is sent to an I/O module, it resets that module and sets the turnaround delay for that module to zero. In each case, the module or modules are initialized to factory default settings if the Snapshot is disabled, and to Snapshot settings if the Snapsot is enabled.

Syntax

!Z

Success Response

A

Error Responses

E_INV_LIMS_GOTSpecified limits invalid for the command.
E_NO_MODULEThere is no module at the specified address.

Refer to FieldPoint Responses for other possible error responses, error numbers, and error descriptions.

Example

>00!Z[checksum][cr]

This example resets the FieldPoint module at address 0 (0x00).