[c]FP-CTR-502
Attributes
| Positions | Attribute Name | [attrMask] Value |
Attribute Setting |
[settings] Value |
|---|---|---|---|---|
| 0–7 (Count Input Channels) |
Terminal Count | 0003 | 065535 | 0000-FFFF |
| Clock Source | 0004 | External Count Input | 00 | |
| Previous Channel | 01 | |||
| 1 khz Reference | 02 | |||
| 32 kHz Reference | 03 | |||
| Gate Source | 0008 | Gate Input 0 | 00 | |
| Gate Input 1 | 01 | |||
| Gate Input 2 | 02 | |||
| Gate Input 3 | 03 | |||
| Always Disabled | 04 | |||
| Always Enabled | 05 | |||
| Read Reset Mode | 0010 | Don't Reset on Read | 00 | |
| Reset on Read | 01 | |||
| Noise Rejection | 0020 | 200 Hz | 03 | |
| 50 kHz | 04 | |||
| 12–15 (Discrete Output Channels) |
Output Source | 0001 | Counter 0 | 00 |
| Counter 1 | 01 | |||
| Counter 2 | 02 | |||
| Counter 3 | 03 | |||
| Counter 4 | 04 | |||
| Counter 5 | 05 | |||
| Counter 6 | 06 | |||
| Counter 7 | 07 | |||
| Discrete Data | 08 | |||
| Output Mode | 0002 | Toggle, Reset Off | 00 | |
| Toggle, Reset On | 01 | |||
| On Pulse | 02 | |||
| Off Pulse | 03 |
Ranges
| Positions | Range | [settings] Value |
|---|---|---|
| 0–7 (Count Input Channels) |
065535 Counts | 40 |
| 8–11 (Discrete Input Channels) |
Boolean | 10 |
| 12–15 (Discrete Output Channels) |
Boolean | 10 |
Commands
| Positions | Command Type | [command type] Value |
Command | [command] Value |
|---|---|---|---|---|
| 0–7 (Count Input Channels) |
Control | 0001 | Reset | 01 |
| Increment | 02 |