Power Up Clear

FieldPoint Optomux Programming

Power Up Clear

[cmdchars] = A

Description

This command should be sent to all network and I/O modules in the system after a power cycle and before any other commands. This command prevents FieldPoint modules from returning error 00, power-up clear expected (E_PONCLR_EXP).

This command functions only if it is the first command sent after power-up. If this command is sent to a module after the first command has been sent, the module responds with a success response. A power-up clear expected error is returned if any other command is sent first. After a power-up clear expected error is returned this command does not need to be sent; the next command executes normally.

This command has no effect on the FieldPoint module operation or setup; the power-up clear expected error provides an indication to the host that there has been a power failure and that the FieldPoint module has been reset to power-up configuration.

Syntax

A

Success Response

A

Error Responses

E_INV_LIMS_GOT Specified limits invalid for the command.

Refer to FieldPoint Responses for other possible error responses, error numbers, and error descriptions.

Example

>33A[checksum][cr]

This example sends Power Up Clear to the FieldPoint module at address 51 (0x33).