[c]FP-SG-140
All addresses are decimal. All byte values are hexadecimal.
Attributes
| Positions | Attribute Name | [attrMask] Value |
Attribute Setting |
[settings] Value |
|---|---|---|---|---|
| 0–7 (Analog Input Channels) |
Noise Rejection | 0001 | 60 Hz | 00 |
| 15 Hz | 09 | |||
| 30 Hz | 0A | |||
| 240 Hz | 0B | |||
| Excitation Voltage | 0002 | 10 V | 00 | |
| 5 V | 01 | |||
| 2.5 V | 02 | |||
| Bridge Completion | 0004 | Half-Bridge Completion OFF | 00 | |
| Half-Bridge Completion ON | 01 |
Ranges
| Positions | Range | [settings] Value |
|---|---|---|
| 0–7 (Analog Input Channels) |
±3.90625 mV/V | 64 |
| ±7.8125 mV/V | 65 | |
| ±31.25 mV/V | 66 | |
| ±62.5 mV/V | 67 |
Commands
The [c]FP-SG-140 does not support any commands.