Analog Input:Temperature:Advanced:Force Read from Channel Property
Short Name: AI.ForceReadFromChan
Property of DAQmx Channel
Specifies whether to read from the channel if it is a cold-junction compensation channel. By default, DAQmx Read does not return data from cold-junction compensation channels. Setting this property to TRUE forces read operations to return the cold-junction compensation channel data with the other channels in the task.
Remarks
The following table lists the characteristics of this property.
Permissions | read/write |
Resettable | yes |
Settable while task is running | device-specific |
Available in Run-Time Engine | yes |