More:Pause:Analog Level:Hysteresis Property

NI-DAQmx Properties

More:Pause:Analog Level:Hysteresis Property

Short Name: Pause.AnlgLvl.Hyst

Property of DAQmx Trigger

Specifies a hysteresis level in the units of the measurement or generation. If Pause.AnlgLvl.When is Above Level, the trigger does not deassert until the source signal passes below Pause.AnlgLvl.Lvl minus the hysteresis. If Pause.AnlgLvl.When is Below Level, the trigger does not deassert until the source signal passes above Pause.AnlgLvl.Lvl plus the hysteresis.

Remarks

The following table lists the characteristics of this property.

Permissionsread/write
Resettableyes
Settable while task is runningdevice-specific
Available in Run-Time Engineyes