Reference:Analog Edge:Hysteresis Property

NI-DAQmx Properties

Reference:Analog Edge:Hysteresis Property

Short Name: Ref.AnlgEdge.Hyst

Property of DAQmx Trigger

Specifies a hysteresis level in the units of the measurement. If Ref.AnlgEdge.Slope is Rising, the trigger does not deassert until the source signal passes below Ref.AnlgEdge.Lvl minus the hysteresis. If Ref.AnlgEdge.Slope is Falling, the trigger does not deassert until the source signal passes above Ref.AnlgEdge.Lvl plus the hysteresis.

Remarks

The following table lists the characteristics of this property.

Permissionsread/write
Resettableyes
Settable while task is runningdevice-specific
Available in Run-Time Engineyes