Counter Input:General Properties:Counter Timebase:Source Property

NI-DAQmx Properties

Counter Input:General Properties:Counter Timebase:Source Property

Short Name: CI.CtrTimebaseSrc

Property of DAQmx Channel

Specifies the terminal of the timebase to use for the counter.

Typically, NI-DAQmx uses one of the internal counter timebases when performing counter measurements. Use this property to specify an external timebase and produce custom measurement ranges that are not possible with the internal timebases.

You also can use this property to chain counters together. By using the output of a counter as the timebase of another counter, you can effectively widen a counter. For example, you can chain two 24 bit counters together to produce one 48 bit counter.

Remarks

The following table lists the characteristics of this property.

Permissionsread/write
Resettableyes
Settable while task is runningdevice-specific
Available in Run-Time Engineyes