Analog Output:General Properties:DAC:Reference Voltage:Connect DAC Reference to Ground Property

NI-DAQmx Properties

Analog Output:General Properties:DAC:Reference Voltage:Connect DAC Reference to Ground Property

Short Name: AO.DAC.Ref.ConnToGnd

Property of DAQmx Channel

Specifies whether to ground the internal DAC reference. Grounding the internal DAC reference has the effect of grounding all analog output channels and stopping waveform generation across all analog output channels regardless of whether the channels belong to the current task. You can ground the internal DAC reference only when AO.DAC.Ref.Src is Internal and AO.DAC.Ref.AllowConnToGnd is TRUE.

Remarks

The following table lists the characteristics of this property.

Permissionsread/write
Resettableyes
Settable while task is runningdevice-specific
Available in Run-Time Engineyes