Start:Analog Edge:Hysteresis Property
Short Name: Start.AnlgEdge.Hyst
Property of DAQmx Trigger
Specifies a hysteresis level in the units of the measurement or generation. If Start.AnlgEdge.Slope is Rising, the trigger does not deassert until the source signal passes below Start.AnlgEdge.Lvl minus the hysteresis. If Start.AnlgEdge.Slope is Falling, the trigger does not deassert until the source signal passes above Start.AnlgEdge.Lvl plus the hysteresis.
Remarks
The following table lists the characteristics of this property.
Permissions | read/write |
Resettable | yes |
Settable while task is running | device-specific |
Available in Run-Time Engine | yes |