Start:Analog Window:Trigger When Property
Short Name: Start.AnlgWin.TrigWhen
Property of DAQmx Trigger
Specifies whether the task starts acquiring or generating samples when the signal enters or leaves the window you specify with Start.AnlgWin.Btm and Start.AnlgWin.Top.
Entering Window (10163) | Trigger when the signal enters the window. |
Leaving Window (10208) | Trigger when the signal leaves the window. |
Remarks
The following table lists the characteristics of this property.
Permissions | read/write |
Resettable | yes |
Settable while task is running | device-specific |
Available in Run-Time Engine | yes |