NI 9203 (FPGA Interface)
CompactRIO 8-Channel, ±20 mA, 16-Bit Analog Input Module
FPGA I/O Node
You can use an FPGA I/O Node, configured for reading, with this device.
Terminals in Software
Use the FPGA I/O Node to access the following terminals for this device.
Terminal | Description |
---|---|
AIx | Analog input channel x, where x is the number of the channel. The NI 9203 has AI channels 0 to 7. |
Arbitration
This device supports only the Arbitrate if Multiple Requestors Only option for arbitration. You cannot configure arbitration settings for this device.
Module Methods
Use the FPGA I/O Method Node to access the following method for this device. This device does not support any I/O methods.
Method | Description |
---|---|
Set Input Range | Sets the input range for a channel as either 0–20 mA or ±20 mA. This method overwrites the value you configure in the C Series Module Properties dialog box. |
I/O Properties
Use the FPGA I/O Property Node to access the following properties for this device.
Property | Description |
---|---|
LSB Weight (±20 mA range) | Returns the LSB weight in pA/LSB for the channel. Use this value to convert and calibrate NI 9203 data if you set the Calibration Mode to Raw in the C Series Module Properties dialog box, and you set the input range to ±20 mA. |
LSB Weight (4–20 mA range) | Returns the LSB weight in pA/LSB for the channel. Use this value to convert and calibrate NI 9203 data if you set the Calibration Mode to Raw in the C Series Module Properties dialog box, and you set the input range to 0–20 mA. |
Module Properties
Use the FPGA I/O Property Node to access the following properties for this device.
Property | Description |
---|---|
Module ID | Returns the module ID. |
Offset (±20 mA range) | Returns the calibration offset in pA for the channel. Use this value to convert and calibrate NI 9203 data if you set the Calibration Mode to Raw in the C Series Module Properties dialog box, and you set the input range to ±20 mA. |
Offset (4–20 mA range) | Returns the calibration offset in pA for the channel. Use this value to convert and calibrate NI 9203 data if you set the Calibration Mode to Raw in the C Series Module Properties dialog box, and you set the input range to 0–20 mA. |
Serial Number | Returns the unique serial number of the module. |
Vendor ID | Returns the National Instruments vendor ID, 0x1093. |
Single-Cycle Timed Loop
This device does not support the single-cycle Timed Loop.
Hardware Documentation
Refer to the NI 9203 Operating Instructions and Specifications to learn about module specifications and how to use the module. Refer to the CompactRIO Related Documentation for further information about CompactRIO documentation.