Cascading Outputs
|
Caution Do not exceed 60 VDC from any terminal to ground when cascading power supplies. |
Because channels 1 and 2 on the NI PXI-4110 are isolated outputs, you can cascade multiple channels in series to generate greater output voltage. For safety reasons, all the terminals must be <60 VDC from ground. Any terminal on the isolated channels can be connected to ground. When you cascade channels in series, the NI PXI-4110 can generate up to 46 V at 1 A, as illustrated in the following figures:
|
Note The NI APS-4100 is required for current above 100 mA. |
|
Caution The NI PXI-4110 does not provide isolation when using CH 0. |
Similarly, you can use the NI PXI-4110 to cascade multiple channels in parallel to generate greater output current. NI recommends cascading no more than two output channels in parallel. Cascade channels 0 and 1 in parallel to generate up to 2 A at 6 V, as shown in the following figure:
|
Note The NI APS-4100 is required for current above 1.1 A in this cascaded configuration. |
|
Note When cascading multiple channels in parallel, verify that all the channels you are cascading are set to output the same voltage level or voltage limit. |
For more information about cascading the outputs of the NI PXI-4110, refer to the NI Developer Zone document, Cascading the Outputs of a DC Power Supply to Extend Voltage and Current Ranges at
ni.com/zone.