Trigger Values
Trigger Unit 1
|
Threshold 1 (R41) default: 1000 |
Here you can specify the threshold level for the trigger source of trigger unit 1. Scaling: Threshold value = full scale value x parameter / resolution Example for KL3361: 16 mV x 1000 / 32767 = 0,488 mV |
Threshold 2 (R42) default: 1000 |
Here you can specify the threshold level for enabling the trigger of trigger unit 1. Scaling: see Threshold 1. |
|
Pulse width (R43) default: 100 |
Here you can specify the pulse width (tP) of trigger unit 1 for the glitch mode. The number of samples (nSP) is entered as the parameter. The pulse width thus depends on the sample rate! Example: - Sample rate: Ts = 200 µs - Samples: nSP = 100 Pulse width : tP = Ts x nSP = 200 µs x 100 = 20 ms |
|
Valid trigger time (R44)
) default: 100 |
Here you can specify the valid trigger time (tVT) for trigger unit 1. The number of valid samples (nVS) is entered as the parameter. The valid trigger time thus depends on the sample rate! Example: - Valid samples: nVS=100 Valid trigger time: tVT = Ts x nVS =200 µs x 100 = 20 ms |
|
Time window active (R40.6) default: not activated |
Here you can switch on the time window for trigger unit 1. |
Trigger Unit 2
![]() |
Threshold 1 (R47) default: 1000 |
Here you can specify the threshold level for the trigger source of trigger unit 2. Scaling: see Trigger Unit 1. |
Threshold 2 (R48) default: 1000 |
Here you can specify the threshold level for enabling the trigger of trigger unit 2. Scaling: see Trigger Unit 1. |
|
Pulse width (R49) default: 100 |
Here you can specify the pulse width for trigger unit 2. Scaling: see Trigger Unit 1. |
|
Valid trigger time (R50)
default: 100 |
Here you can specify the valid trigger time for trigger unit 2. Scaling: see Trigger Unit 1. |
|
Time window active (R46) default: not activated |
Here you can switch on the time window for trigger unit 2. |
Trigger unit 3 (KL3362 only)
See Trigger Unit 1.
Trigger unit 4 (KL3362 only)
See Trigger Unit 2.