BECKHOFF KL3362: Mounting and Wiring |
Connecting the KL3362
The diagram shows the connection of two function generators (FG1, FG2) to the channels of the KL3362 oscilloscope terminal.
Contact | No | Connection |
---|---|---|
+24V | 1 | Supply voltage for digital output |
OUT 24V | 2 | Digital output |
IN 1 | 3 | Oscilloscope input channel 1 ( -10 V to +10 V) |
GND | 4 | Ground for oscilloscope input channel 1 (internally connected with terminal no. 8) |
24V Trigger | 5 | Trigger input |
0V | 6 | Ground for trigger input |
IN 2 | 7 | Oscilloscope input channel 2 ( -10 V to +10 V) |
GND | 8 | Ground for oscilloscope input channel 2 (internally connected with terminal no. 4) |