BECKHOFF KL3361, KL3362: KS2000 Configuration Software |
General Settings
Operation mode
Pre-Trigger (R32.8-10) | Recording ceases as soon as a trigger event occurs. | |
Mid-Trigger (R32.8-10) | The trigger event is the centre of the recording. | |
Post-Trigger (R32.8-10) default |
Recording commences as soon as a trigger event occurs. | |
Fast-Sampling (R32.8-10) | Operation with increased sampling rate of up to 10µs:
|
|
Trigger delay active (R32.4) default: not activated |
Switches the trigger delay on. | |
Trigger delay (R52) default: 0 |
A trigger delay (tTD) can be specified here. The number of skipped samples (nSTD) is entered as the parameter. The trigger delay thus depends on the sample rate! Example: - Sample rate: Ts = 200 µs - skipped samples: nSTD=100 tTD = Ts x nSTD = 200 µs x 100 = 20 ms |
|
Test mode active (R32.5)) default: not activated |
Switches the test mode on. In test mode, a ramp is output instead of converted analog values. It runs from 0 to 0x3FFF and back again. | |
Auto trigger active (R32.6) default: not activated |
Switches the auto trigger function on. With auto trigger switched on, the trigger unit is automatically activated once the preceding event has been evaluated. To this end, bit 0 is toggled in status register 1 (SR1) with each new evaluation. |
General
Sample-Rate (R35) default: 200 µs |
Interval (Ts) between two samples (scans) in microseconds. The sampling speed is limited to Ts =100 µs (10 kHz) by the evaluation of the trigger detectors. Only the Fast sampling mode enables sampling at Ts =10 µs (100 kHz). |
Sample-Amount (R36) default: 100 |
Number of sampling values to be recorded. A maximum of 4,000 values can be recorded. |
Trigger frequency (R56) default: 0 |
Here you can specify the trigger frequency of the timer. |
Scale channel 1
User offset (R33) default: 0 |
Here you can enter an offset. Scaling: offset = full scale value x parameter / resolution Example for KL3361: 16 mV x 100 / 32767 = 0.049 mV |
|
User gain (R34) default: 256 |
Here you can enter the gain factor for scaling the input value by this factor. |
Scaling channel 2 (KL3362 only)
User offset (R33) default: 0 |
Here you can enter an offset. Scaling: offset = full scale value x parameter / resolution Example for KL3361: 16 mV x 100 / 32767 = 0.049 mV |
|
User gain (R34) default: 256 |
Here you can enter the gain factor for scaling the input value by this factor. |