| Technical data |
KL3361 |
| Number of inputs |
1 analog, 1 trigger |
| Signal voltage UB |
-16 mV to +16 mV |
| Input resistance |
> 1 MOhm (UB) |
| Supply voltage for the measuring bridge UV |
5 VDC, maximum 20 mA |
| Resolution |
14 bit (plus 1 bit sign) |
| Sampling rate (configurable) |
minimum 100 µs, (minimum 10 µs for fast sampling) |
| Measurement error (complete measuring range) |
±1% of the full scale value |
| Internal memory |
32 Kbytes |
| Bit width in the input process image |
2 data words, 1 control byte |
| Bit width in the output process image |
2 data words, 1 status byte |
| Power supply for the electronics |
via the K-Bus |
| Current input from the K-Bus with external supply of the measuring bridge |
typically 120 mA |
| Current input from the K-Bus with supply of the measuring bridge (4 x 350 Ohm) via KL3361 |
typically 140 mA |
| Dielectric strength |
500 Vrms (shielding, base plate / K-Bus) |
| Permissible ambient temperature range during operation |
0°C ... +55°C |
| Permissible ambient temperature range during storage |
-25 °C ... +85°C |
| Permissible relative humidity |
95%, no condensation |
| Vibration / shock resistance |
conforms to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29 |
| EMC resistance burst / ESD |
conforms to EN 61000-6-2 / EN 61000-6-4 |
| Weight |
approx. 55 g |
| Dimensions (W x H x D) |
approx. 15mm x 100 mm x 70 mm |
| Assembly |
on 35 mm C mounting rail according to EN 50022 |
| Installation position |
variable |
| Type of protection |
IP20 |
| Approval |
CE |