| BECKHOFF KL3132, KL3162, KL3172, KL3182: Product Overview |
Technical Data
| Technical data | KL3132 | KL3162 | KL3172 | KL3182 |
|---|---|---|---|---|
| Number of inputs | 2 | |||
| Signal voltage | -10 V ... +10 V | 0 ... 10 V | 0 ... 2 V | -2 V ... +2 V |
| Input resistance | > 200 kΩ | |||
| Common-mode voltage UCM | ±10 V | |||
| Resolution | 16 bits | |||
| Conversion time | 140 ms, configurable | |||
| Meas. error (total meas. range) | ±0.05% of the full scale value, self-calibration | |||
| Bit width in the K-Bus I/O | 2 x 16 bit user data (optionally 2 x 8 bit control/status) | |||
| Bit width in the input process image | 2 data words, 2 status byte | |||
| Bit width in the output process image | 2 data words, 2 control byte | |||
| Power supply for the electronics | via the K-Bus | |||
| Electrical isolation | 500 Vrms (differential input / K-Bus) | |||
| Connection | spring force technology | |||
| Current consumption from the K-Bus | typically 85 mA | |||
| Weight | app. 55 g | |||
| Dimensions (w x h x d) | app. 15mm x 100mm x 70mm (aligned width: 12 mm) | |||
| Assembly | on 35 mm mounting rail according to EN 50022 | |||
| Permissible ambient temperature range during operation | 0°C... + 55°C | |||
| Permissible ambient temperature range during storage | -25°C... + 85°C | |||
| Permissible relative humidity | 95%, no condensation | |||
| Vibration / shock resistance | according to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29 | |||
| EMC resistance burst / ESD | according to EN 61000-6-2 / EN 61000-6-4 | |||
| Protection class | IP 20 | |||
| Installation position | variable | |||
| Approval | CE | |||