KL3132, KL3142, KL3152, KL3162, KL3172, KL3182 - KS2000-Settings

BECKHOFF KL31x2

 
BECKHOFF KL3172: Configuration Software KS2000

Settings

A dialog mask for the parameterization of the KL3172 can be found under Settings.

Operation mode

Channel disabled (R32.11)

You disable this cannel here, to get faster cycle time for the other channel (the default is not disabled).
A disabled channel is indicated by its switched off Run and Error LED.

User scaling active (R32.0)

You can activate user scaling here (the default is deactivated).

Manufacturer scaling active (R32.1)

You can activate manufacturer scaling here (the default is deactivated).

Watchdog timer active (R32.2)

You can deactivate the watchdog timer here (the default is activated).

Signed amount representation (R32.3)

You can activate the signed amount representation here (the default is deactivated).

Siemens output format (R32.4)

You can activate Siemens output format here (the default is deactivated).

Calibration active (R32.5)

You can deactivate the calibration here (the default is activated).

Differential measurement (R32.6)

You can deactivate the differential measurement here (the default is activated).

Stabilization of calibration active (R32.7)

You can deactivate the stabilization of the calibration here (the default is activated).

Overrange protection (R32.8)

You can deactivate the overrange protection here (the default is activated).

Threshold 1 active (R32.9)

You can activate the threshold 1 here (the default is deactivated).

Threshold 2 active (R32.10)

You can activate the threshold 2 here (the default is deactivated).

Register values

User offset (R33)

You can specify the user offset between -32768 and 32767 here (default: 0).

User gain (R34)

You can specify the user gain between -0 and 65535 here (default: 256, corresponding to a factor of 1).

Calibration interval (R40)

You can specify the calibration interval for the reference signal here in steps of 100 ms (the default is 300 s).

Forced calibration interval (R44)

You can specify the interval for the forced calibration here. This interval is always a multiple (the default is 3dec) of the calibration interval. The interval for forced calibration when the terminal leaves the factory is therefore 3 x 180 s = 900 s.

Number of stable measured values (R47)

You can specify the number of measured values used for the calibration here (default: 50).

Tolerance for measured value stability (R48)

You can specify the stable measured value tolerance for the calibration here (default: 5).

Threshold 1 (R35)

You can specify the threshold 1 here (default: 0).

Threshold 2 (R36)

You can specify the threshold 2 here (default: 0).

Filter constant (R37.11-R37.4)

The filter constant SF specifies the 3dB limit frequency of the sinc3 filter (the default is 860dec).

Fast-Step Mode(TM) enabled (R37.0)

You can activate Fast Step Mode here (the default is deactivated). A fast reaction to jumps at the input follows in fast step mode, in spite of the filter stage being active. In this case the filter is bypassed!

FIR filter enabled (R37.1)

You can deactivate the FIR filter here (the default is activated).