BECKHOFF KL3142, KL3152: Product Overview |
Technical Data
Technical data | KL3142 | KL3152 |
---|---|---|
Number of inputs | 2 | |
Signal voltage | 0 ... 20 mA | 4 ... 20 mA |
Input resistance | 100 Ω shunt | |
Common-mode voltage UCM | ±10 V | |
Resolution | 16 bits | |
Conversion time | 140 ms | |
Meas. error (total meas. range) | ±0.05% of the full scale value, self-calibration | |
Bit width in the K-Bus I/O | 2 x 16 bit user data (optionally 2 x 8 bit control/status) | |
Bit width in the input process image | 2 data words, 2 status byte | |
Bit width in the output process image | 2 data words, 2 control byte | |
Power supply for the electronics | via the K-Bus | |
Electrical isolation | 500 Vrms (differential input / K-Bus) | |
Connection | spring force technology | |
Current consumption from the K-Bus | typically 85 mA | |
Weight | app. 55 g | |
Dimensions (w x h x d) | app. 15mm x 100mm x 70mm (aligned width: 12 mm) | |
Assembly | on 35 mm mounting rail according to EN 50022 | |
Permissible ambient temperature range during operation | 0°C... + 55°C | |
Permissible ambient temperature range during storage | -25°C... + 85°C | |
Permissible relative humidity | 95%, no condensation | |
Vibration / shock resistance | according to EN 60068-2-6 / EN 60068-2-27, EN 60068-2-29 | |
EMC resistance burst / ESD | according to EN 61000-6-2 / EN 61000-6-4 | |
Protection class | IP 20 | |
Installation position | variable | |
Approval | CE |