CompactRIO 32-Channel Single-Ended/16-Channel Differential, ±200 mV to ±10 V, 16-Bit Analog Input Module


Module I/O Variables

To use I/O from this module in a VI, drag and drop I/O variables from the Project Explorer window to the block diagram of the VI. The I/O variables for the channels return calibrated floating-point data in volts.

Module Channels

The NI 9205 has the following channels.

Channel Description
AIx Analog input channel x, where x is the number of the channel. For the NI 9205, x is 0 to 31.

C Series Module Properties Dialog Box

Use this dialog box to configure the NI 9205. Right-click the NI 9205 in the Project Explorer window and select Properties to display this dialog box. You can configure the following options.

  • Name—Specifies the name of the C Series module, which appears in the Project Explorer window. LabVIEW assigns a default name to the module based on the slot number. You can use this field to give the module a descriptive name.
  • Module Type—Specifies the type of C Series module. You cannot change this value.
  • Location—Specifies a slot in the chassis for the C Series module.
  • Channel Configuration—You can specify the input range for each channel.
    • Channels—Specifies the channel(s) for which you want to select the input range.
    • Input Range—Specifies the input range for the selected channel(s) as ±10 V, ±5 V, ±1 V, or ±200 mV.
    • Terminal Mode—Specifies the terminal mode for the selected channel(s) as RSE (referenced single-ended), NRSE (nonreferenced single-ended), or DIFF (differential).

Hardware Documentation

Refer to the NI 9205 Operating Instructions and Specifications to learn about module specifications and how to use the module. Refer to the CompactRIO Related Documentation (Scan Interface) topic for further information about CompactRIO documentation.