Inrush Current Protection
To limit inrush current, an impedance, such as a resistor, can be placed in series between Cint2 and Cexternal. This resistor isolates the unwanted effects of the load capacitance and limits damage to the relay contacts. A protection resistance, Rp, should be selected such that
V/Rp< switching current rating of the relay
The following figures illustrate the use of the protection resistor Rp.
Resistor Rp Added to Limit Current into Cexternal
Current Graph Comparison
The energy associated with the inrush currents in these two circuits can be expressed as
Ewithout protection= ½(Cint2+Cext)V2=525 nJ
and
Ewith protection= ½(Cint2)V2=25 nJ
Note Although the peak currents are the same, the associated energy for the protected circuit is 21 times less. |