[SENSe:]TEMPerature:TRANsducer:RTD:TYPE

From Keysight 34970A/34972A

[SENSe:]TEMPerature:TRANsducer:RTD:TYPE
[SENSe:]TEMPerature:TRANsducer:FRTD:TYPE

Syntax

[SENSe:]TEMPerature:TRANsducer:RTD:TYPE <type>[,(@<ch_list>)]
[SENSe:]TEMPerature:TRANsducer:RTD:TYPE? [(@<ch_list>)]

[SENSe:]TEMPerature:TRANsducer:FRTD:TYPE <type>[,(@<ch_list>)]
[SENSe:]TEMPerature:TRANsducer:FRTD:TYPE? [(@<ch_list>)]

Description

This command selects the RTD type for 2-wire (RTD) or 4-wire (FRTD) temperature measurements on the specified channels.

Used With:

  • 34901A   20 Channel Multiplexer (2/4-wire) Module
  • 34902A   16 Channel Multiplexer (2/4-wire) Module
  • 34908A   40 Channel Single-Ended Multiplexer Module (RTD only; not FRTD)

Parameters

Name Type Range of Values Default Value
<type> Discrete {85|91} This is a required parameter.
<ch_list> Channel List

One or more channels, as shown:

(@310) - channel 10 on the module in slot 300.

(@305:310) - channels 05 through 10 on the module in slot 300.

(@202:207,209,302:308) - channels 02 through 07 and 09 on the module in slot 200 and channels 02 through 08 on the module in slot 300.

If you omit the optional <ch_list> parameter, this command applies to the currently defined scan list.

Remarks

  • For 4-wire resistance measurements, the instrument automatically pairs channel n in Bank 1 with channel n+10 in Bank 2 (34901A) or n+8 (34902A) to provide the source and sense connections. For example, make the source connections to the HI and LO terminals on channel 02 in Bank 1 and the sense connections to the HI and LO terminals on channel 12 (34901A) or 10 (34902A) in Bank 2.Specify the paired channel in Bank 1 (source) as the <ch_list> channel (channels in Bank 2 are not allowed in the <ch_list>).
  • The instrument supports RTDs with Alpha = 0.00385 (DIN/IEC 751) using ITS-90 software conversions or Alpha = 0.00391 using IPTS-68 software conversions.
  • "PT100" is a special label that is sometimes used to refer to an RTD with Alpha = 0.00385 and Ro = 100Ω.
  • The instrument sets the RTD type to "85" after a Factory Reset (*RST command). An Instrument Preset (SYSTem:PRESet command) or Card Reset (SYSTem:CPON command) does not change the setting.

Return Format

The query returns +85 or +91. Multiple results are separated by commas.

Examples

In the following examples, you could substitute the node name FRTD for the node name RTD.

The following command sets the transducer type to 85 on the channels shown.

[SENSe:]TEMPerature:TRANsducer:RTD:TYPE 85,(@301:305)

 

The following query returns the transducer type on the channels shown.

[SENSe:]TEMPerature:TRANsducer:RTD:TYPE? (@202,204,301:305,308)

Typical Response: +85,+91,+85,+85,+85,+85,+85,+91

See Also

SENSe Subsystem Introduction