[c]FP-CTR-502

FieldPoint cFP-180x Modbus

[c]FP-CTR-502

All addresses are decimal. All byte values are hexadecimal.

Attributes

Channel
(Type)
Least Significant
Digits of Address
Name Setting Value
Counter n
(Count Input)
8n Range 0–65535 Counts 40
Terminal Count LSB
(Least Significant Byte)
0–65535 00-FF
8n + 1 Terminal Count MSB
(Most Significant Byte)
00-FF
Clock Source External Count Input00
Previous Channel01
1 khz Reference02
32 kHz Reference03
8n + 2 Gate Source Gate Input 000
Gate Input 101
Gate Input 202
Gate Input 303
Always Disabled04
Always Enabled05
Read Reset Mode Don't Reset on Read00
Reset on Read01
8n + 3 Noise Rejection 200 Hz03
50 kHz04
Reserved — 00
Gate n
(Discrete Input)
8n + 64 Range Boolean 10
Reserved — 00
Output n
(Discrete Output)
8n + 96 Range Boolean 10
Output Source Counter 000
Counter 101
Counter 202
Counter 303
Counter 404
Counter 505
Counter 606
Counter 707
Discrete Data08
8n + 97 Output Mode Toggle, Reset Off00
Toggle, Reset On01
On Pulse02
Off Pulse03
Reserved — 00

Commands

Channel
(Type)
Least Significant
Digits of Address
Name Setting Value
Count n
(Count Input)
8n Control Reset01
Increment02
Reserved — 00