[c]FP-TC-120
All addresses are decimal. All byte values are hexadecimal.
Attributes
| Channel (Type) |
Least Significant Digits of Address |
Name | Setting | Value |
|---|---|---|---|---|
| Analog Input n | 8n | Range | ±50 mV | 0A |
| ±25 mV | 0B | |||
| 20 to 80 mV | 0C | |||
| ±100 mV | 0D | |||
| 02048 K | 20 | |||
| 270 to 1770 °C | 21 | |||
| 454 to 3218 °F | 22 | |||
| Thermocouple Type | J | 00 | ||
| K | 01 | |||
| T | 02 | |||
| E | 03 | |||
| R | 04 | |||
| S | 05 | |||
| N | 06 | |||
| B | 07 | |||
| CJ Temperature (Analog Input) |
64 | Range | 223358 K | 23 |
| -50 to 85 °C | 24 | |||
| 58 to 185 °F | 25 | |||
| CJ Temperature | Internal | 00 | ||
| 0 °C | 01 | |||
| 25 °C | 02 |
Commands
The [c]FP-TC-120 does not support any commands.