[c]FP-TC-120

FieldPoint I/O Module

[c]FP-TC-120

All ID values are hexadecimal.

Module ID

0107

Channel Status

Message ID
Out of range 01
Open thermocouple 02

Ranges

Name ID
±50 mV 0A
±25 mV 0B
–20 to 80 mV 0C
±100 mV 0D
0–2048 K 20
–270 to 1770 °C 21
–454 to 3218 °F 22

Attributes

Attribute Name Attribute ID Attribute Value Attribute ID

Thermocouple Type

02

J 00
K 01
T 02
E 03
R 04
S 05
N 06
B 07

CJC Source

03

Internal 00
0 °C 01
25 °C 02

No Commands